How to make it - Slider - Safety - Hamido

002: Power Supply for Fire Control Panels – Siemens

Power Supply for Fire Detection & Alarm Control Panels:

We need electrical convertors to have a desired power (Voltage, Current, Frequency etc.) according to our requirement in fire alarm system. Converter as the name implies, converts the main voltage to a required system voltage for the main board or other components.

Nowadays power supplies apart from converting the mains voltage to system voltage provide below items as well:

  • Monitor mains voltage
  • Monitor the batteries
  • Provide fault signal
  • Provide relay output
  • Provide separated and isolated outputs (for example 24 V)

Case Study: Siemens

As a case study we review the power supplies (converters) used in the Siemens fire alarm systems.

Note:

To choose Siemens products, you should pay attention to the type of system, production series, manufacturer's recommendation and your local standards. The following information is to show an overview and sharing experiences. Finally, you should get updated information from the official website of the company or one of the product distributors and technical service providers in your area.

Siemens Cerberus FIT / Cerberus PRO (EN) / Sinteso / XC10:

Model Part Number Input (V AC) Output (V DC) Current (A) Dimension (mm) Weight (Kg) Power (W)
FCP1001 A6E60500051 --- --- --- --- --- ---
FCP1004-E A6E60500054 115/230 28VDC 3.5 A --- --- 105
FP2015-A1 S54400-B121-A1 97…127/196…253 --- Max. 2.5 95 x 170 x 54 --- 70
FP2003-A1 A5Q00016005 85... 265 VAC --- 0.5… 1 A 95 x 170 x 54 --- 70
FP2004-A1 A5Q00020825 115...230 --- 2.6 / 1.2 130 x 150 x 70 --- 150, A
FP2005-A1 A5Q00018779 115... 230 --- 2.6 / 1.2 130 x 150 x 70 --- 150, B
SV24V-150W V24230-Z6-A5 115... 230 --- 2.6 / 1.2 130 x 150 x 70 --- 150
FP120-Z1 S54400-S122-A1 97…127/196…253 --- Max. 2.5 430 x 399 x 124 3,920 70
FDUL221-B A5Q00008437 --- --- --- --- --- ---
  • Current mentioned in the above tables are for permanent load.
  • FCP1004-E is for XC10 and FC10 panels
  • FP2004-A1 can be ordered for empty housing.
  • FP2005-A1 is for cascading purpose (to add to an existing power supply and provide more current)
  • SV24V-150W is used for ordering the spare power supply for replacement. (without accessories)
  • FP120-Z1 is a standalone power supply (kit).
  • FDUL221-B is a part number of spare adapter for loop tester (FDUL221)

Siemens Cerberus PRO (UL) / Cerberus PRO Modular (UL):

Model Part Number Input (V AC) Output (V DC) Current (A) Dimension (mm) Weight (Kg) Power Supply (W)
FP2011-U1 500-450222 120VAC @ 50/60 Hz

240VAC @ 50/60 Hz

24VDC 6.5 19.7x9.8x4.5 1.361 170
FP2012-U1 S54400-Z60-A1 120VAC @ 50/60 Hz

240VAC @ 50/60 Hz

24VDC 11.5 25x9.8x6.4 1.814 300
PSC-12M S54430-C26-A1 120VAC @ 50/60 Hz

220VAC @ 50/60 Hz

240VAC @ 50/60 Hz

24VDC 12 --- ---  
PSX-12M S54430-C27-A1 120VAC @ 50/60 Hz

220VAC @ 50/60 Hz

240VAC @ 50/60 Hz

24VDC 12 --- ---  
  • Power supply PSC-12M is a main and PSX-12M is an extender.
  • PSFA is a power supply filter assembly.
  • FCA2032-U1 is a battery disconnect module which is designed to disconnect the battery while voltage drops below 19VDC.

Siemens Algorex:

Model Part Number Input (V AC) Output (V DC) Current (A) Dimension (mm) Weight (Kg) Power Supply (W)
B1F120 4952330001 115/230 24 3 140 x 100 x 38 0.567 ---
B2F060 5112850001 115/230 24 4.5 210 x 100 x 40 0.685 ---
B2F020 A5Q00025281 115/230 29.6 6 210 x 100 x 40 0.770 ---
B2F040 5102990001 115/230 29.6 3.5 210 x 100 x 40 0.660 ---
  • B2F020 and B2F040 needs battery plug-in module E3C... or control panel plug-in module E3X...

Siemens Synova:

Model Part Number Input (V AC) Output (V DC) Current (A) Dimension (mm) Weight (Kg) Power Supply (W)
B2F020 BPZ:4705880001 115/230 29.6 6 --- --- ---
  • B2F020 needs battery plug-in module E3C... or control panel plug-in module E3X...

Notes:

  • Please note that according to standard you will need the emergency battery (for back up) and battery charger option for converter.

Filters:

  • In old series of Siemens (Algorex and Synova) there was also Filters as an additional protection parts for power supplies. Using the filters helps power supply to provide a standard Voltage, Current and Frequency.
  • Normally Filters considered as an additional protection. For example against RF interference on the power line.
Filter Description Model Part Number Voltage (V AC) Current (A) Weight (kg)
Mains filter B3P020 A5Q00008751 250 6 0.150

Independent Battery Charger:

Old Power supplies need an external board for battery charging and monitoring the main voltage and batteries. But new generation of converters equipped with battery charger and can monitor the situation of the emergency batteries as well.

Description Model Part Number Note
Plug-in battery charging module E3C011 5054790001 For Algorex and Synova

Other suppliers:

For external power supply you can also use standard power supply from other manufacturers. Below you can find some samples:

Manufacturer Model P.N Input (V AC) Output (V DC) Current (A) Dimension (mm) Weight (Kg) Power Supply (W) Battery charger
Meanwell HDR-30-24 HDR-30-24 220 24 1.5 9.65 x 6.35 x 4.5 0.120 30 NO
Meanwell MDR-60-24 MDR-60-24 100-240 24 2.5 4.5 x 10.3 x 11.2 0.3 60 NO
Meanwell HDR-100-24 HDR-100-24 85-264 24 3 7.5 x 10.5 x 6.5 0.27 92 NO
Meanwell LRS-100-24 LRS-100-24 85...373 24 4.5 13.4 x 10.4 x 3.8 0.320 108 NO
Meanwell NDR-120-24 NDR-120-24 90...264 24 5 14.99 x 14.48 x 6.35 0.36 120 NO
RSP FA24VRPS FA24VRPS 110/220 24 5 19 x 3.99 x 8.99 0.399 120 NO
Meanwell HDR-150-24 HDR-150-24 85...264 24 6.25 11.6 x 10.6 x 6.4 0.340 150 NO
RSP FA24VRPS FA24VRPS 110/220 24 10 21.01 x 11 x 5.99 0.599 240 NO
Meanwell DRP-240-24 DRP-240-24 85…264 24 10 12.52 x 12.52 x 10 1.2 240 NO
Meanwell LRS-350-24 LRS-350-24 180-264 24 --- 21.47 x 11.47 x 2.97 0.760 350 NO
Meanwell RSP-500-24 RSP-500-24 24 21 28 x 14 x 6 1.3 500 NO

Leave a Reply

Your email address will not be published. Required fields are marked *