Offshore cables are usually used in non-dry areas with moisture, pollution, and corrosive chemicals.
General Features:
- Power, control, instrumentation, telecommunication, and earth cables
- Performance in harsh environments (heat, cold, humidity, chemical reaction, vibration etc.)
- Fire resistance or flame retardant
- Low smoke
- Halogen free
- Mud resistant
- Conductor (stranded tinned copper: protection against rust or aluminum)
Cable Identification according to NEK 606:
This is a Norwegian standard in the offshore field, but it is also used globally. Usually cables in this standard are identified with 2 or 4 letters. For instrumentation cables there are also other additional letters.
1- Insulation
-
- B: Fire resistance tape (such as Mica tape) + Insulation (Halogen-free)
- R: EPR (Ethylene Propylene Rubber)
- T: XLPE (Cross Linked Polyethylene)
- I: Thermoplastic compound (Halogen-free)
- U: Halogen-free thermoset compound EMA or EVA
- A: Fibre, tight buffered
- Q: Fibre in loose tube
2-Bedding/Inner Covering inner sheath
-
- F: Bedding/Inner covering or taping (Halogen-free)
- Y: Screen (poss. with PE or PP)
- I: Thermoplastic compound (Halogen-free) SHF1
Note:
Inner sheath for protection against moisture, Fire-retardant and halogen-free material
3-Armour/Screen
-
- L: Aluminium (laminated to outer jacket)
- X: No armour
- O: Copper wire braid (tinned or bare)
- A: Strength member of yarn
- C: Galvanized steel wire braid
Note:
-
- Armour for protection against mechanical damage
- Shield for protection against electromagnetic interference
4- Outer Jacket
-
- I: Thermoplastic compound (Halogen-free) SHF1
- U: Halogen-free thermoset compound, SHF2
- U: Halogen-free mud resistant thermoset compound, SHF Mud
Note:
Outer jacket for protection against damage, moisture, dust, dirt, salt corrosion, oil etc.
5- Additional letter for instrumentation cables:
-
- (c): Collective screen
- (i): Individual pair or triple screen
Common offshore cables:
- BU
- RU
- BFOU
- RFOU
- BFOU(i)
- BFOU(c)
- RFOU(i)
- RFOU(c)
Color identifications:
- x1 Conductor: Natural
- x2 Conductors: Blue + Brown
- x3 Conductors: Brown + Black + Grey
- x4 Conductors: Brown + Black + Grey + Blue
- x5 Conductors or more: White Numbered
The following features are very important in installing above cables:
- Light weight
- Small diameter
- Flexibility
- Elasticity
Standards:
- NEK 606 (NEK: Norsk Elektroteknisk Komite)
- BS6883
- IEEE 1580
- IEC60331 (fire resistance)
- IEC60332-1, IEC60332-3-22 (flame retardancy)
- IEC60754-1 (halogen free)
- IEC 61034-1 (low smoke)
- IEC 60092 (oil resistance/mud resistance)
Approvals:
- DNV (DNV GL)
- DNV (Det Norske Veritas)
- GL (Germanischer LIoyd)
- ABS
- CCS
Related links:
- OEUK (UKOOA)