How to make it - Slider - Safety - Hamido

286: Fire alarm system end of lines – Siemens

The main purpose of using the EOLS (end of lines) in fire alarm system is line monitoring.

Different types of EOLs:

  • Resistors
  • Capacitors
  • Diodes

EOLs in Fire Alarm System – Siemens:

Note:

To choose Siemens products, you should pay attention to the type of system, production series, manufacturer's recommendation and your local standards. The following information is to show an overview and sharing experiences. Finally, you should get updated information from the official website of the company or one of the product distributors and technical service providers in your area.

Resistors:

Resistors  Specifications Application
120R XTO2001-A1
470R XC10
560R FDCIO223
680R FDCIO223, XC10
820R XC10
910R XCI2005-A1
1k15 FDCIO222
1k2 XC10
2k2 500mW FC72x or FC20xx main board
2k7 FDCIO223
3k01 500mW FC72x or FC20xx Main board, FDCIO222
3K3 FDCIO223, XC10
6k2 (6k6) For sounder flashers (parallel)
EOL22(Ex) FDCIO223

Diodes:

Diodes  Specifications Application
1N4007 1000V/1A FC72x Main board, FC12x Main board (monitoring)
1N4004 280V XC10, For sounder flashers (common minus)
1.5KE20CA 2047V / 2202V XC10, FDCIO223
P6KE18CA 18V TVS, IO9A XC10, FC12x (zones)

Capacitors:

Capacitors  Specifications Application
10 μF 10 μF FC12x (GB Continuity)

Devices (Siemens):

Device EOLs
FC72x or FC20xx main board Resistors (2.2k, 3k), Diode (IN4007)
FDCIO222 Resistors (3k, 1.15k)
FDCIO223 Resistors (560, 680, 2.7k, 3.3k), Diode (1.5KE20CA)

Leave a Reply

Your email address will not be published. Required fields are marked *

Warning: Trying to access array offset on null in /home/.sites/71/site5011221/web/wp-content/themes/disto/single.php on line 265