Power cables with plastic insulation and plastic sheath:
According to DIN VDE 0262, DIN VDE 0263, DIN VDE 0265, DIN VDE 0266, DIN VDE 0267, DIN VDE 0271, DIN VDE 0273 and DIN VDE 0276 part 603, 604, 620, 622 and 626
1- Identifications of designation
- N: DIN VDE standard (Cables are acc. to standard)
- (N): Similar to DIN VDE standard
2- Conductor material
- A: Aluminium
- - (no code): Copper
3- Insulating material
- Y: Polyvinyl chloride (PVC)
- 2Y: Thermoplastic polyethylene (PE)
- X: Cross-linked polyvinyl chloride (XPVC)
- 2X: Cross-linked polyethylene (XLPE)
- H - Field limiting conductive layers over the conductor and over the Insulation
- HX - Insulation of cross-linked halogen-free polymer blend
- (no code): Impregnated paper
4- Concentric conductor (screen/shielding)
- C: Concentric copper conductor
- CW: Concentric copper conductor in waveconal formation
- CE: Concentric copper conductor over each individual core
- S: Screen of copper wires (Braided copper)
- SE: Screen of copper wires over each individual core
- H: Conductive layers
- F - Overhead line cable (DIN VDE 0276)
- FE - Insulation sustaining
- (F): Longitudinally water proof screen
5- Armouring
- B: Steel tape armouring
- F: Armour of galvanized flat steel wires
- R: Armour of galvanized round steel wires
- G: Counter helix of galvanized steel tape
6- Sheath material
- Y - Inner sheath of polyvinylchloride (PVC)
- Y - Outer sheath of polyvinylchloride (PVC)
- 1Y - Outer sheath of polyurethane (PUR)
- 2Y - Outer sheath of polyethylene (PE)
- X: Cross-linked polyvinyl chloride (XPVC)
- 2X: Cross-linked polyethylene (XLPE)
- HX - Sheath of cross-linked halogen-free polymer blend
- A: Fiberglass
- K: Lead
- KL: Aluminium
7- Protective conductor
- J: With protective conductor
- O: Without protective conductor
8- Number of cores
9- Conductor cross section in mm2
10- Conductor type
- R- : Circular conductor
- S- : Sector conductor
- O- : Oval conductor
- -E: Solid conductor
- -M: Strand conductor
- -H: Hollow circular conductor (Waveguide)
- RE: Circular conductor, solid
- RM:Circular conductor, stranded
- SE: Sector shaped conductor, solid
- SM: Sector shaped conductor, stranded
- OM: Oval shaped conductor, stranded
- /V: Compacted conductor
11- Rating voltage
- 0.6/1 kV
- 3.6/6 kV
- 6/10 kV
- 12/20 kV
- 18/30 kV
- 20/35 kV
- 40/69 kV
- 64/110 kV
- 76/132 kV
Related standards