How to make it - Slider - Electrical - Hamido

057: Cable gland selection for electrical cabinets

Cable gland fix the cable at incoming/outgoing of electrical cabinets and also seal the box to prevent the dust, dirt or small insects from entering.

Cable gland material:

  1. PVC (Polyvinyl chloride)
  2. Nylon (Polyamide 6)
  3. Nickel plated brass
  4. Stainless steel (304 and 316L material)

Cable gland type:

  1. EMC (with Electromagnetic Compatibility)
  2. Double Compression
  3. Armoured (for wire braid cables in a hazardous area)
  4. Explosion Proof (ATEX)
  5. Breathable (avoiding the condensation formation)
  6. Liquid Tight Connector
  7. Spiral Flexible

Sample 1:

Note: There are some differences in the diameter between various manufacturers.

Gland M Major Diameter X Pitch Clamping cable size range Thread Length Combined Length Spanner Size
(mm) (mm) Min. (mm) Max. (mm) GL mm mm mm
M12X1.5 M 12 X 1.5 3 6,5 7 19 14
M16X1.5 M 16 X 1.5 4 8 8 20 19
M18X1.5 M 18 X 1.5 5 10 8 21 21
M20X1.5 M 20 X 1.5 6 12 8 22 22
M22X1.5 M 22 X 1.5 10 14 8 23 24
M24X1.5 M 24 X 1.5 10 14 9 25 27
M25X1.5 M 25 X 1.5 10 14 9 25 27
M25X1.5 M 25 X 1.5 13 18 9 27 30
M27X1.5(2) M 27 X 1.5(2) 13 18 9 27 30
M28X1.5(2) M 28 X 1.5(2) 13 18 9 27 30
M30X1.5(2) M 30 X 1.5(2) 13 18 9 29 32/34
M32X1.5(2) M 32 X 1.5(2) 15 22 10 29 36
M33X1.5(2) M 33 X 1.5(2) 15 22 10 29 36
M36X1.5(2) M 36 X 1.5(2) 18 25 10 31 40
M37X1.5(2) M 37 X 1.5(2) 18 25 10 31 40
M40X1.5(2) M 40 X 1.5(2) 18 25 11 31 45
M42X1.5(2) M 42 X 1.5(2) 22 30 11 35 45
M47X1.5(2) M 47 X 1.5(2) 25 33 11 37 50
M48X1.5(2) M 48 X 1.5(2) 25 33 11 37 50/52
M50X1.5(2) M 50 X 1.5(2) 32 38 12 37 55
M54X1.5(2) M 54 X 1.5(2) 32 38 12 38 57
M56X1.5(2) M 56 X 1.5(2) 32 38 12 38 60
M60X1.5(2) M 60 X 1.5(2) 37 44 13 38 64
M63X1.5(2) M 63 X 1.5(2) 37 44 13 38 65/68
M64X1.5(2) M 64 X 1.5(2) 37 44 13 38 65/68
M72X1.5(2) M 72 X 1.5(2) 42 52 15 42 75
M80X1.5(2) M 80 X 1.5(2) 55 56 15 45 85
M88X1.5(2) M 88 X 1.5(2) 65 70 15 45 95
M100X1.5(2) M 100 X 1.5(2) 78 84 15 45 110

 

Sample 2:

Note: There are some differences in the diameter between various manufacturers.

XLPE (Cross Linked Polyethylene) / SWA (Steel Wire Armour) / PVC (Polyvinylchlorid) Cable and PVC Sheated
Cable Size Conductor Numbers of cores:
Cable cross-section area Neutral 1 2 3 3 1/2 4 5 7 10 12 19 27 37 48
(mm²)
1,5 ….. ….. 20S 20S ….. 20S 20S 20S 20 25 25 32 32 32
2,5 ….. ….. 20S 20S ….. 20S 20S 20 25 25 32 32 40 40
4 & 6 ….. ….. 20S 20S ….. 20 20 25 25 25 32 40 40 50S
10 ….. ….. 20 20 ….. 20 ….. ….. ….. ….. ….. ….. ….. …..
16 ….. ….. 20 25 ….. 25 ….. ….. ….. ….. ….. ….. ….. …..
25 16 ….. 25 25 ….. 25 ….. ….. ….. ….. ….. ….. ….. …..
35 16 ….. 25 25 32 25 ….. ….. ….. ….. ….. ….. ….. …..
50 25 25 32 32 32 32 ….. ….. ….. ….. ….. ….. ….. …..
70 35 25 25 32 32 32 ….. ….. ….. ….. ….. ….. ….. …..
95 50 25 32 32 40 40 ….. ….. ….. ….. ….. ….. ….. …..
120 70 32 32 40 50S 50S ….. ….. ….. ….. ….. ….. ….. …..
150 70 32 40 40 50S 50 ….. ….. ….. ….. ….. ….. ….. …..
185 95 32 40 63S 50 40 ….. ….. ….. ….. ….. ….. ….. …..
240 120 40 50S 50 63 63S ….. ….. ….. ….. ….. ….. ….. …..
300 150 40 50 63S 75S 63 ….. ….. ….. ….. ….. ….. ….. …..
300 18S 40 63S 63 75S 75S ….. ….. ….. ….. ….. ….. ….. …..
400 18S 50S 63S 63 75 75 ….. ….. ….. ….. ….. ….. ….. …..
500 ….. 50 63S 75S ….. 75 ….. ….. ….. ….. ….. ….. ….. …..
630 ….. 50 ….. ….. ….. ….. ….. ….. ….. ….. ….. ….. ….. …..
800 ….. 63S ….. ….. ….. ….. ….. ….. ….. ….. ….. ….. ….. …..
10000 ….. 63 ….. ….. ….. ….. ….. ….. ….. ….. ….. ….. ….. …..

 

Sample 3:

Note: There are some differences in the diameter between various manufacturers.

SWA (Steel Wire Armour) Cables: Based on cables manufactured according to BS standard
Cable Size Conductor Numbers of cores:
Cable cross-section area 1 2 3 4 5 7 10 12 19 27 37 48
(mm²)
1,5 ….. 20S 20S 20S 20S 20 20 25 25 32 32 32
2,5 ….. 20S 20S 20S 20 20 25 25 25 32 40 40
4 ….. 20S 20S 20 20 20 25 25 32 40 40 50
6 ….. 20 20 20 20 ….. ….. ….. ….. ….. ….. …..
10 ….. 20 20 25 25 ….. ….. ….. ….. ….. ….. …..
16 ….. 25 25 25 25 ….. ….. ….. ….. ….. ….. …..
25 ….. 25 32 32 32 ….. ….. ….. ….. ….. ….. …..
35 ….. 32 32 32 40 ….. ….. ….. ….. ….. ….. …..
50 20 25 32 32 50 ….. ….. ….. ….. ….. ….. …..
70 20 32 32 40 50 ….. ….. ….. ….. ….. ….. …..
95 25 32 40 50S ….. ….. ….. ….. ….. ….. ….. …..
120 25 40 50S 50 ….. ….. ….. ….. ….. ….. ….. …..
150 32 40 50s 50 ….. ….. ….. ….. ….. ….. ….. …..
185 32 50S 50 63S ….. ….. ….. ….. ….. ….. ….. …..
240 32 50 63S 63 ….. ….. ….. ….. ….. ….. ….. …..
300 40 63S 63 75S ….. ….. ….. ….. ….. ….. ….. …..
400 40 63S 75S 75 ….. ….. ….. ….. ….. ….. ….. …..

 

Sample 4:

Note: There are some differences in the diameter between various manufacturers.

PVC (Polyvinylchlorid) SWA (Steel Wire Armour)  Cable
Cable Size Conductor Numbers of cores:
Cable cross-section area 1 2 3 4 5 7 10 12 19 27 37 48
(mm²)
1,5 ….. ….. ….. 20S 20S 20S 20 20 25 25 32 32
2,5 ….. 20S 20S 20S 20S 20 25 25 25 32 32/40 40
4 ….. 20S 20S 20 20 25 25 25 32 40 ….. …..
6 ….. 20 20 20 ….. ….. ….. ….. ….. ….. ….. …..
10 ….. 25 25 25 ….. ….. ….. ….. ….. ….. ….. …..
16 ….. 25 0,25 25 ….. ….. ….. ….. ….. ….. ….. …..
25 ….. 25 25/32 32 ….. ….. ….. ….. ….. ….. ….. …..
35 ….. 25/32 32 32/40 ….. ….. ….. ….. ….. ….. ….. …..
50 20 32 32 32/40 ….. ….. ….. ….. ….. ….. ….. …..
70 25 32 40 40 ….. ….. ….. ….. ….. ….. ….. …..
95 25 40 40 50 ….. ….. ….. ….. ….. ….. ….. …..
120 25 40 50 50 ….. ….. ….. ….. ….. ….. ….. …..
150 32 40 50 50 ….. ….. ….. ….. ….. ….. ….. …..
185 32 50 50 63 ….. ….. ….. ….. ….. ….. ….. …..
240 40 50 63 63 ….. ….. ….. ….. ….. ….. ….. …..
300 40 63 63 75 ….. ….. ….. ….. ….. ….. ….. …..
400 50 63 75 75 ….. ….. ….. ….. ….. ….. ….. …..
500 50 ….. ….. ….. ….. ….. ….. ….. ….. ….. ….. …..
630 50 ….. ….. ….. ….. ….. ….. ….. ….. ….. ….. …..
800 63 ….. ….. ….. ….. ….. ….. ….. ….. ….. ….. …..
10000 63 ….. ….. ….. ….. ….. ….. ….. ….. ….. ….. …..

 